Abstract: In recent year, with recent increase of interest towards leisure sports, increased number of Zip-Line or Zip-Wire facilities has built. Many researches have been actively conducted on the emphasis of the cable and the wire at the bridge. However, very limited researches have been conducted on the safety of the Zip-Line structure. In fact, fall accidents from Zip-Line have been reported frequently. Therefore, in this study, the structural safety of Zip-Line under dynamic impact loading condition were evaluated on the previously installed steel cable for leisure (Zip-Line), using 3-dimensional nonlinear Finite Element (FE) model. The result from current study would assist assurance of systematic stability of Zip-Line.
Abstract: This paper deals with a novel approach of power
transformers diagnostics. This approach identifies the exact location
and the range of a fault in the transformer and helps to reduce
operation costs related to handling of the faulty transformer, its
disassembly and repair. The advantage of the approach is a
possibility to simulate healthy transformer and also all faults, which
can occur in transformer during its operation without its
disassembling, which is very expensive in practice. The approach is
based on creating frequency dependent impedance of the transformer
by sweep frequency response analysis measurements and by 3D FE
parametrical modeling of the fault in the transformer. The parameters
of the 3D FE model are the position and the range of the axial short
circuit. Then, by comparing the frequency dependent impedances of
the parametrical models with the measured ones, the location and the
range of the fault is identified. The approach was tested on a real
transformer and showed high coincidence between the real fault and
the simulated one.