Investigating Performance of Numerical Distance Relay with Higher Order Antialiasing Filter

This paper investigates the impact on operating time delay and relay maloperation when 1st,2nd and 3rd order analog antialiasing filters are used in numerical distance protection. RC filter with cut-off frequency 90 Hz is used. Simulations are carried out for different SIR (Source to line Impedance Ratio), load, fault type and fault conditions using SIMULINK, where the voltage and current signals are fed online to the developed numerical distance relay model. Matlab is used for plotting the impedance trajectory. Investigation results shows that, about 75 % of the simulated cases, numerical distance relay operating time is not increased even-though there is a time delay when higher order filters are used. Relay maloperation (selectivity) also reduces (increases) when higher order filters are used in numerical distance protection.





References:
<p>[1] Brigham. E. Oran, The Fast Fourier Transform. Englewood Cliffs, NJ: Prentice-Hall, 1974.
[2] M. Adamiak et al., &ldquo;Advancements in adaptive algorithms for secure high speed distance protection,&rdquo; in 23rd Annual Western Protective Relaying Conference, 1996.
[3] D. Hou, &ldquo;Relay element performance during power system frequency excursions,&rdquo; in 61st Annual Conference for Protective Relay Engineers, pp. 105 &ndash;117, Apr. 2008.
[4] S. G. A. Perez, &rdquo;Modelling Relays for Power System Protection Studies,&rdquo; Ph.D. dissertation, Dept. Elect. Engg., Saschkatchewan Univ., Canada, 2006.
[5] A. Sweetana, &ldquo;Transient response characteristics of capacitive potential devices,&rdquo; IEEE Transactions on Power Apparatus and Systems, vol. PAS-90, pp. 1989&ndash;2001, Sep 1971.
[6] B. Kasztenny et al., &ldquo;Distance relays and capacitive voltage transformers balancing speed and transient overreach,&rdquo; in 53rd Annu. Conf. for Protective Relay Engineering, Ontario, Canada, Apr. 2000.
[7] A. G. Phadke and J. S. Thorp. John Wiley &amp; Sons, Ltd, Jul 2009.
[8] S. M. Brahma, P. L. De Leon, and R. G. Kavasseri, &ldquo;Investigating the option of removing the antialiasing filter from digital relays,&rdquo; IEEE Trans. Power Del., vol. 24, pp. 1864&ndash;1868, Oct 2009.
[9] J. Izykowski, B. Kasztenny, E. Rosolowski, M. Saha, and B. Hillstrom, &ldquo;Dynamic compensation of capacitive voltage transformers,&rdquo; IEEE Trans. Power Del., vol. 13, no. 1, pp. 116&ndash;122, Jan. 1998.
[10] G. Benmouyal, &ldquo;Removal of dc-offset in current waveforms using digital mimic filtering,&rdquo; IEEE Trans. Power Del., vol. 10, no. 2, pp. 621&ndash;630, Apr. 1995.</p>