Abstract: This paper presents the voltage regulation scheme of
D-STATCOM under three-phase faults. It consists of the voltage
detection and voltage regulation schemes in the 0dq reference. The
proposed control strategy uses the proportional controller in which
the proportional gain, kp, is appropriately adjusted by using genetic
algorithms. To verify its use, a simplified 4-bus test system is situated
by assuming a three-phase fault at bus 4. As a result, the DSTATCOM
can resume the load voltage to the desired level within
1.8 ms. This confirms that the proposed voltage regulation scheme
performs well under three-phase fault events.
Abstract: The aim of this study is to develop a cost-effective WBGT heat stress monitor which provides precise heat stress measurement. The proposed device employs SHT15 and DS18B20 as a temperature and humidity sensors, respectively, incorporating with ATmega328 microcontroller. The developed heat stress monitor was calibrated and adjusted to that of the standard temperature and humidity sensors in the laboratory. The results of this study illustrated that the mean percentage error and the standard deviation from the measurement of the globe temperature was 2.33 and 2.71 respectively, while 0.94 and 1.02 were those of the dry bulb temperature, 0.79 and 0.48 were of the wet bulb temperature, and 4.46 and 1.60 were of the relative humidity sensor. This device is relatively low-cost and the measurement error is acceptable.
Abstract: This paper presents the DC voltage control design of D-STATCOM when the D-STATCOM is used for load voltage regulation. Although, the DC voltage can be controlled by active current of the D-STATCOM, reactive current still affects the DC voltage. To eliminate this effect, the control strategy with elimination effect of the reactive current is proposed and the results of the control with and without the elimination the effect of the reactive current are compared. For obtaining the proportional and integral gains of the PI controllers, the symmetrical optimum and genetic algorithms methods are applied. The stability margin of these methods are obtained and discussed in detail. In addition, the performance of the DC voltage control based on symmetrical optimum and genetic algorithms methods are compared. Effectiveness of the controllers designed was verified through computer simulation performed by using Power System Tool Block (PSB) in SIMULINK/MATLAB. The simulation results demonstrated that the DC voltage control proposed is effective in regulating DC voltage when the DSTATCOM is used for load voltage regulation.
Abstract: This paper describes a finite-difference time-domainFDTD) method to analyze lightning surge propagation in electric transmission lines. Numerical computation of solving the Telegraphist-s equations is determined and investigated its effectiveness. A source of lightning surge wave on power transmission lines is modeled by using Heidler-s surge model. The
proposed method was tested against medium-voltage power
transmission lines in comparison with the solution obtained by using
lattice diagram. As a result, the calculation showed that the method is one of accurate methods to analyze transient
lightning wave in power transmission lines.
Abstract: This paper presents an application of power line
carrier (PLC) for electrical power telemetering. This system has a
special capability of transmitting the measured values to a centralized
computer via power lines. The PLC modem as a passive high-pass
filter is designed for transmitting and receiving information. Its
function is to send the information carrier together with transmitted
data by superimposing it on the 50 Hz power frequency signal. A
microcontroller is employed to function as the main processing of the
modem. It is programmed for PLC control and interfacing with other
devices. Each power meter, connected via a PLC modem, is assigned
with a unique identification number (address) for distinguishing each
device from one another.
Abstract: Optimal routing in communication networks is a
major issue to be solved. In this paper, the application of Tabu Search
(TS) in the optimum routing problem where the aim is to minimize
the computational time and improvement of quality of the solution in
the communication have been addressed. The goal is to minimize the
average delays in the communication. The effectiveness of Tabu
Search method is shown by the results of simulation to solve the
shortest path problem. Through this approach computational cost can
be reduced.
Abstract: Installation of power compensation equipment in
some cases places additional buses into the system. Therefore, a total
number of power flow equations and voltage unknowns increase due
to additional locations of installed devices. In this circumstance, power flow calculation is more complicated. It may result in a
computational convergence problem. This paper presents a power flow calculation by using Newton-Raphson iterative method together
with the proposed load transfer technique. This concept is to eliminate additional buses by transferring installed loads at the new buses to existing two adjacent buses. Thus, the total number of power
flow equations is not changed. The overall computational speed is
expectedly shorter than that of solving the problem without applying the load transfer technique. A 15-bus test system is employed for test
to evaluate the effectiveness of the proposed load transfer technique. As a result, the total number of iteration required and execution time
is significantly reduced.