Abstract: In this paper, a detailed simulation model of a solar-powered triple-effect LiBr–H2O absorption chiller is developed to supply both cooling and heating demand of a large-scale building, aiming to reduce the fossil fuel consumption and greenhouse gas emissions in building sector. TRNSYS 17 is used to simulate the performance of the system over a typical year. A combined energetic-economic-environmental analysis is conducted to determine the system annual primary energy consumption and the total cost, which are considered as two conflicting objectives. A multi-objective optimization of the system is performed using a genetic algorithm to minimize these objectives simultaneously. The optimization results show that the final optimal design of the proposed plant has a solar fraction of 72% and leads to an annual primary energy saving of 0.69 GWh and annual CO2 emissions reduction of ~166 tonnes, as compared to a conventional HVAC system. The economics of this design, however, is not appealing without public funding, which is often the case for many renewable energy systems. The results show that a good funding policy is required in order for these technologies to achieve satisfactory payback periods within the lifetime of the plant.
Abstract: In most existing buildings in hot climate, cooling
loads lead to high primary energy consumption and consequently
high CO2 emissions. These can be substantially decreased with
integrated renewable energy systems. Kuwait is characterized by its
dry hot long summer and short warm winter. Kuwait receives annual
total radiation more than 5280 MJ/m2 with approximately 3347 h of
sunshine. Solar energy systems consist of PV modules and parabolic
trough collectors are considered to satisfy electricity consumption,
domestic water heating, and cooling loads of an existing building.
This paper presents the results of an extensive program of energy
conservation and energy generation using integrated photovoltaic
(PV) modules and Parabolic Trough Collectors (PTC). The program
conducted on an existing institutional building intending to convert it
into a Net-Zero Energy Building (NZEB) or near net Zero Energy
Building (nNZEB). The program consists of two phases; the first
phase is concerned with energy auditing and energy conservation
measures at minimum cost and the second phase considers the
installation of photovoltaic modules and parabolic trough collectors.
The 2-storey building under consideration is the Applied Sciences
Department at the College of Technological Studies, Kuwait. Single
effect lithium bromide water absorption chillers are implemented to
provide air conditioning load to the building. A numerical model is
developed to evaluate the performance of parabolic trough collectors
in Kuwait climate. Transient simulation program (TRNSYS) is
adapted to simulate the performance of different solar system
components. In addition, a numerical model is developed to assess
the environmental impacts of building integrated renewable energy
systems. Results indicate that efficient energy conservation can play
an important role in converting the existing buildings into NZEBs as
it saves a significant portion of annual energy consumption of the
building. The first phase results in an energy conservation of about
28% of the building consumption. In the second phase, the integrated
PV completely covers the lighting and equipment loads of the
building. On the other hand, parabolic trough collectors of optimum
area of 765 m2 can satisfy a significant portion of the cooling load,
i.e about73% of the total building cooling load. The annual avoided
CO2 emission is evaluated at the optimum conditions to assess the
environmental impacts of renewable energy systems. The total annual
avoided CO2 emission is about 680 metric ton/year which confirms
the environmental impacts of these systems in Kuwait.
Abstract: The thermal performance of a solar water heating with
1.00 m2 flat plate collectors in Cascavel - PR, is which presented in
this article, paper presents the solution to leverage the marketing of
solar heating systems through detailed constituent materials of the
solar collector studies, these abundant materials in construction, such
as expanded polyethylene, PVC, aluminum and glass tubes, mixing
them with new materials to minimize loss of efficiency while
decreasing its cost. The system was tested during months and the
collector obtained maximum recorded temperature of outlet fluid of
55°C, while the maximum temperature of the water at the bottom of
the hot water tank was 35°C. The average daily energy collected was
19.6 MJ/d; the energy supplied by the solar plate was 16.2 MJ/d; the
loss in the feed pipe was 3.2 MJ/d; the solar fraction was 32.2%, the
efficiency of the collector was 45.6% and the efficiency of the system
was 37.8%.