Investigating the Effect of Using Capacitors in the Pumping Station on the Harmonic Contents (Case Study: Kafr El - Shikh Governorate, Egypt)

Power Factor (PF) is one of the most important parameters in the electrical systems, especially in the water pumping station. The low power factor value of the water pumping stations causes penalty for the electrical bill. There are many methods use for power factor improvement. Each one of them uses a capacitor on the electrical power network. The position of the capacitors is varied depends on many factors such as; voltage level and capacitors rating. Adding capacitors on the motor terminals increase the supply power factor from 0.8 to more than 0.9 but these capacitors cause some problems for the electrical grid network, such as increasing the harmonic contents of the grid line voltage. In this paper the effects of using capacitors in the water pumping stations to improve the power factor value on the harmonic contents of the electrical grid network are studied. One of large water pumping stations in Kafr El-Shikh Governorate in Egypt was used, as a case study. The effect of capacitors on the line voltage harmonic contents is measured. The station uses capacitors to improve the PF values at the 1 lkv grid network. The power supply harmonics values are measured by a power quality analyzer at different loading conditions. The results showed that; the capacitors improved the power factor value of the feeder and its value increased than 0.9. But the THD values are increased by adding these capacitors. The harmonic analysis showed that; the 13th, 17th, and 19th harmonics orders are increased also by adding the capacitors.

Assessing the Problems of Pumping Stations: A Case Study of Boneh Basht Pumping Station

Establishing pumping stations is one of the most common ways of providing water from rivers. There are many issues involved in the design and operation of pumping stations most important of which is the problem of sedimentation. One of the significant issues which must be taken into consideration in designing pumping stations is the operation method and technical matters related to it. Safety and convenience of operation is one of the issues that must be always considered by the designer. Some of the major issues in making decisions regarding the type of design for the station are geographical condition, the location of the station and availability of experts in maintenance and operation of the station. Dimensions of the station must allow free movement for checking and operating pumps after installation of pumps and plumbing system.