Abstract: South Africa is experiencing an exponential growth of distributed solar PV installations. This is due to various factors with the predominant one being increasing electricity tariffs along with decreasing installation costs, resulting in attractive business cases to some end-users. Despite there being a variety of economic and environmental advantages associated with the installation of PV, their potential impact on distribution grids has yet to be thoroughly investigated. This is especially true since the locations of these units cannot be controlled by Network Service Providers (NSPs) and their output power is stochastic and non-dispatchable. This report details two case studies that were completed to determine the possible voltage and technical losses impact of increasing PV penetration in the Northern Cape of South Africa. Some major impacts considered for the simulations were ramping of PV generation due to intermittency caused by moving clouds, the size and overall hosting capacity and the location of the systems. The main finding is that the technical impact is different on a constrained feeder vs a non-constrained feeder. The acceptable PV penetration level is much lower for a constrained feeder than a non-constrained feeder, depending on where the systems are located.
Abstract: This paper presents an application of Artificial Neural
Network (ANN) algorithm for improving power system voltage
stability. The training data is obtained by solving several normal and
abnormal conditions using the Linear Programming technique. The
selected objective function gives minimum deviation of the reactive
power control variables, which leads to the maximization of
minimum Eigen value of load flow Jacobian. The considered reactive
power control variables are switchable VAR compensators, OLTC
transformers and excitation of generators. The method has been
implemented on a modified IEEE 30-bus test system. The results
obtain from the test clearly show that the trained neural network is
capable of improving the voltage stability in power system with a
high level of precision and speed.
Abstract: Optimization and control of reactive power
distribution in the power systems leads to the better operation of the
reactive power resources. Reactive power control reduces
considerably the power losses and effective loads and improves the
power factor of the power systems. Another important reason of the
reactive power control is improving the voltage profile of the power
system. In this paper, voltage and reactive power control using
Neural Network techniques have been applied to the 33 shines-
Tehran Electric Company. In this suggested ANN, the voltages of PQ
shines have been considered as the input of the ANN. Also, the
generators voltages, tap transformers and shunt compensators have
been considered as the output of ANN. Results of this techniques
have been compared with the Linear Programming. Minimization of
the transmission line power losses has been considered as the
objective function of the linear programming technique. The
comparison of the results of the ANN technique with the LP shows
that the ANN technique improves the precision and reduces the
computation time. ANN technique also has a simple structure and
this causes to use the operator experience.
Abstract: Electricity market activities and a growing demand for electricity have led to heavily stressed power systems. This requires operation of the networks closer to their stability limits. Power system operation is affected by stability related problems, leading to unpredictable system behavior. Voltage stability refers to the ability of a power system to sustain appropriate voltage levels through large and small disturbances. Steady-state voltage stability is concerned with limits on the existence of steady-state operating points for the network. FACTS devices can be utilized to increase the transmission capacity, the stability margin and dynamic behavior or serve to ensure improved power quality. Their main capabilities are reactive power compensation, voltage control and power flow control. Among the FACTS controllers, Static Var Compensator (SVC) provides fast acting dynamic reactive compensation for voltage support during contingency events. In this paper, voltage stability assessment with appropriate representations of tap-changer transformers and SVC is investigated. Integrating both of these devices is the main topic of this paper. Effect of the presence of tap-changing transformers on static VAR compensator controller parameters and ratings necessary to stabilize load voltages at certain values are highlighted. The interrelation between transformer off nominal tap ratios and the SVC controller gains and droop slopes and the SVC rating are found. P-V curves are constructed to calculate loadability margins.
Abstract: Based on the component approach, three kinds of
dynamic load models, including a single –motor model, a two-motor
model and composite load model have been developed for the
stability studies of Khuzestan power system. The study results are
presented in this paper. Voltage instability is a dynamic phenomenon
and therefore requires dynamic representation of the power system
components. Industrial loads contain a large fraction of induction
machines. Several models of different complexity are available for
the description investigations. This study evaluates the dynamic
performances of several dynamic load models in combination with
the dynamics of a load changing transformer. Case study is steel
industrial substation in Khuzestan power systems.
Abstract: In this paper, we apply the PQ theory with shunt active power filter in an unbalanced and distorted power system voltage to compensate the perturbations generated by non linear load. The power factor is also improved in the current source. The PLL system is used to extract the fundamental component of the even sequence under conditions mentioned of the power system voltage.