Abstract: This paper presents optimal Phasor Measurement Unit (PMU) Placement in network using a genetic algorithm approach as it is infeasible and require high installation cost to place PMUs at every bus in network. This paper proposes optimal PMU allocation considering observability and redundancy utilizing Genetic Algorithm (GA) approach. The nonlinear constraints of buses are modeled to give accurate results. Constraints associated with Zero Injection (ZI) buses and radial buses are modeled to optimize number of locations for PMU placement. GA is modeled with ZI bus constraints to minimize number of locations without losing complete observability. Redundancy of every bus in network is computed to show optimum redundancy of complete system network. The performance of method is measured by Bus Observability Index (BOI) and Complete System Observability Performance Index (CSOPI). MATLAB simulations are carried out on IEEE -14, -30 and -57 bus-systems and compared with other methods in literature survey to show the effectiveness of the proposed approach.
Abstract: This paper presents state estimation with Phasor Measurement Unit (PMU) allocation to obtain complete observability of network. A matrix is designed with modeling of zero injection constraints to minimize PMU allocations. State estimation algorithm is developed with optimal allocation of PMUs to find accurate states of network. The incorporation of PMU into traditional state estimation process improves accuracy and computational performance for large power systems. The nonlinearity integrated with zero injection (ZI) constraints is remodeled to linear frame to optimize number of PMUs. The problem of optimal PMU allocation is regarded with modeling of ZI constraints, PMU loss or line outage, cost factor and redundant measurements. The proposed state estimation with optimal PMU allocation has been compared with traditional state estimation process to show its importance. MATLAB programming on IEEE 14, 30, 57, and 118 bus networks is implemented out by Binary Integer Programming (BIP) method and compared with other methods to show its effectiveness.
Abstract: This paper presents a Generalized Binary Integer Linear Programming (GBILP) method for optimal allocation of Phasor Measurement Units (PMUs) and to generate Dynamic State Estimation (DSE) solution with complete observability. The GBILP method is formulated with Zero Injection Bus (ZIB) constraints to reduce the number of locations for placement of PMUs in the case of normal and single line contingency. The integration of PMU and conventional measurements is modeled in DSE process to estimate accurate states of the system. To estimate the dynamic behavior of the power system with proposed method, load change up to 40% considered at a bus in the power system network. The proposed DSE method is compared with traditional Weighted Least Squares (WLS) state estimation method in presence of load changes to show the impact of PMU measurements. MATLAB simulations are carried out on IEEE 14, 30, 57, and 118 bus systems to prove the validity of the proposed approach.
Abstract: This paper presents a methodology using
Gravitational Search Algorithm for optimal placement of Phasor
Measurement Units (PMUs) in order to achieve complete
observability of the power system. The objective of proposed
algorithm is to minimize the total number of PMUs at the power
system buses, which in turn minimize installation cost of the PMUs.
In this algorithm, the searcher agents are collection of masses which
interact with each other using Newton’s laws of gravity and motion.
This new Gravitational Search Algorithm based method has been
applied to the IEEE 14-bus, IEEE 30-bus and IEEE 118-bus test
systems. Case studies reveal optimal number of PMUs with better
observability by proposed method.
Abstract: Low frequency power oscillations may be triggered
by many events in the system. Most oscillations are damped by the
system, but undamped oscillations can lead to system collapse.
Oscillations develop as a result of rotor acceleration/deceleration
following a change in active power transfer from a generator. Like
the operations limits, the monitoring of power system oscillating
modes is a relevant aspect of power system operation and control.
Unprevented low-frequency power swings can be cause of cascading
outages that can rapidly extend effect on wide region. On this regard,
a Wide Area Monitoring, Protection and Control Systems
(WAMPCS) help in detecting such phenomena and assess power
system dynamics security. The monitoring of power system
electromechanical oscillations is very important in the frame of
modern power system management and control. In first part, this
paper compares the different technique for identification of power
system oscillations. Second part analyzes possible identification
some power system dynamics behaviors Using Wide Area
Monitoring Systems (WAMS) based on Phasor Measurement Units
(PMUs) and wavelet technique.