Abstract: The use of synthetic retardants in polymeric insulated
cables is not uncommon in the high voltage engineering to study
electrical treeing phenomenon. However few studies on organic
materials for the same investigation have been carried. .This paper
describes the study on the effects of Oil Palm Empty Fruit Bunch
(OPEFB) microfiller on the tree initiation and propagation in silicone
rubber with different weight percentages (wt %) of filler to insulation
bulk material. The weight percentages used were 0 wt % and 1 wt %
respectively. It was found that the OPEFB retards the propagation of
the electrical treeing development. For tree inception study, the
addition of 1(wt %) OPEFB has increase the tree inception voltage of
silicone rubber. So, OPEFB is a potential retardant to the initiation
and growth of electrical treeing occurring in polymeric materials for
high voltage application. However more studies on the effects of
physical and electrical properties of OPEFB as a tree retardant
material are required.
Abstract: Measurements of capacitance C and dissipation
factor tand of the stator insulation system provide useful information
about internal defects within the insulation. The index k is defined as
the proportionality constant between the changes at high voltage of
capacitance DC and of the dissipation factor Dtand . DC and
Dtand values were highly correlated when small flat defects were
within the insulation and that correlation was lost in the presence of
large narrow defects like electrical treeing. The discrimination
between small and large defects is made resorting to partial discharge
PD phase angle analysis. For the validation of the results, C and tand
measurements were carried out in a 15MVA 4160V steam turbine
turbogenerator placed in a sugar mill. In addition, laboratory test
results obtained by other authors were analyzed jointly. In such
laboratory tests, model coil bars subjected to thermal cycling resulted
highly degraded and DC and Dtand values were not correlated. Thus,
the index k could not be calculated.
Abstract: This paper presents the experimental results on effect of applied voltage stress frequency to the occurrence of electrical treeing in 22 kV cross linked polyethylene (XLPE) insulated cable.Hallow disk of XLPE insulating material with thickness 5 mm taken from unused high voltage cable was used as the specimen in this study. Stainless steel needle was inserted gradually into the specimen to give a tip to earth plane electrode separation of 2.50.2 mm at elevated temperature 105-110°C. The specimen was then annealed for 5 minute to minimize any mechanical stress build up around the needle-plane region before it was cooled down to room temperature. Each specimen were subjected to the same applied voltage stress level at 8 kV AC rms, with various frequency, 50, 100, 500, 1000 and 2000 Hz. Initiation time, propagation speed and pattern of electrical treeing were examined in order to study the effect of applied voltage stress frequency. By the experimental results, initial time of visible treeing decreases with increasing in applied voltage frequency. Also, obviously, propagation speed of electrical treeing increases with increasing in applied voltage frequency.Furthermore, two types of electrical treeing, bush-like and branch-like treeing were observed.The experimental results confirmed the effect of voltage stress frequency as well.