Abstract: The paper presents the impact of work on the electric arc furnace. Arc equipment is one of the largest receivers powered by the power system. Electric arc disturbances arising during melting process occurring in these furnaces are the cause of an abrupt change of the passive power of furnaces. Currents drawn by these devices undergo an abrupt change, which in turn cause voltage fluctuations and light flicker. The quantitative evaluation of the voltage fluctuations is now the basic criterion of assessment of an influence of unquiet receiver on the supplying net. The paper presents the method of determination of range of voltage fluctuations and light flicker at parallel operation of arc devices. The results of measurements of voltage fluctuations and light flicker indicators recorded in power supply networks of steelworks were presented, with different number of parallel arc devices. Measurements of energy quality parameters were aimed at verifying the proposed method in practice. It was also analyzed changes in other parameters of electricity: the content of higher harmonics, asymmetry, voltage dips.
Abstract: In technological processes, in addition to the main
product, result a large amount of materials, called wastes, but due to
the possibilities of recovery, by means of recycling and reusing it can
fit in the category of by-products. These large amounts of dust from
the steel industry are a major problem in terms of environmental and
human health, landscape, etc. Solving these problems, the impressive
amounts of waste can be done through their proper management and
recovery for every type of waste. In this article it was watched the
capitalizing through pelleting and briquetting of small and powdery
waste aiming to obtain the sponge iron as raw material, used in blast
furnaces and electric arc furnaces. The data have been processed in
the Excel spreadsheet program, being presented in the form of
diagrams.
Abstract: Voltage flicker problems have long existed in several
of the distribution areas served by the Taiwan Power Company. In
the past, those research results indicating that the estimated ΔV10
value based on the conventional method is significantly smaller than
the survey value. This paper is used to study the relationship between
the voltage flicker problems and harmonic power variation for the
power system with electric arc furnaces. This investigation discussed
thought the effect of harmonic power fluctuation with flicker
estimate value. The method of field measurement, statistics and
simulation is used. The survey results demonstrate that 10 ΔV
estimate must account for the effect of harmonic power variation.
Abstract: Voltage flicker is a disturbance in electrical power
systems. The reason for this disturbance is mainly the large nonlinear
loads such as electric arc furnaces. Synchronous static
compensator (STATCOM) is considered as a proper technique to
mitigate the voltage flicker. Application of more suitable and precise
power electronic converter leads to a more precise performance of the
compensator. In this paper a three-level 12-pulse voltage source
inverter (VSI) with a 12-terminal transformer connected to the ac
system is studied and the obtained results are compared with the
performance of a STATCOM using a simple two-level VSI and an
optimal and more precise performance of the proposed scheme is
achieved.