Abstract: This paper presents a scheme for the protection of loop system from all type of faults using the direction of fault current. The presence of distributed generation in today’s system increases the complexity of fault detection as the power flow is bidirectional. Hence, protection scheme specific to this purpose needs to be developed. This paper shows a fast protection scheme using communication which can be fiber optic or wireless. In this paper, the possibility of wireless communication for protection is studied to exchange the information between the relays. The negative sequence and positive sequence directional elements are used to determine the direction of fault current. A PSCAD simulation is presented and validated using commercial SEL relays.
Abstract: In this paper, monitoring and control of tap changer
mechanism of a transformer implementation in an Intelligent
Electronic Device (IED) is discussed. It has been a custom for
decades to provide a separate panel for on load tap changer control
for monitoring the tap position. However, this facility cannot either
record or transfer the information to remote control centers. As there
is a technology shift towards the smart grid protection and control
standards, the need for implementing remote control and monitoring
has necessitated the implementation of this feature in numerical
relays. This paper deals with the programming, settings and logic
implementation which is applicable to both IEC 61850 compatible
and non-compatible IEDs thereby eliminating the need for separate
tap changer control equipment. The monitoring mechanism has been
implemented in a 28MVA, 110 /6.9kV transformer with 16 tap
position with GE make T60 IED at Ultratech cement limited
Gulbarga, Karnataka and is in successful service.