Abstract: This paper discusses aspects of outages in the electric transmission network in the Kosovo Power System caused by the atmospheric discharges.
Frequency and location of the atmospheric discharges in Kosovo territory will be provided by a lightning location system ALARM (Automated Lightning Alert and Risk Management) and from the data from the Meteorological Department in Prishtina International Airport. These data will be used to make comparisons with the actual outages registered in the Kosovo Power System from the Kosovo Transmission, systems and market operator (KOSTT) during a specific time period.
The lines with the worst performance determined, regarding the atmospheric discharges, will be choose for further discussions in terms of over voltages caused by the direct or indirect lightning strokes.
Recommendations for protection in terms of insulator coordination and surge arresters will be given at the end and in this stage dynamic simulation will take part.
Abstract: This paper discusses aspects of re-design of loadshedding
schemes with respect to actual developments in the Kosovo
power system. Load-shedding is a type of emergency control that is
designed to ensure system stability by reducing power system load to
match the power generation supply. This paper presents a new
adaptive load-shedding scheme that provides emergency protection
against excess frequency decline, in cases when the Kosovo power
system might be disconnected from the regional transmission
network. The proposed load-shedding scheme uses the local
frequency rate information to adapt the load-shedding pattern to suit
the size and location of the occurring disturbance. The proposed
scheme is tested in a software simulation on a large scale PSS/E
model which represents nine power system areas of Southeast Europe
including the Kosovo power system.