Abstract: This paper presents the electrical effect of two neighboring distribution substation during the construction phase. The size of auxiliary grounding grid have an effect on entire grounding system. The bigger the size of auxiliary grounding grid, the lower the GPR and maximum touch voltage, with the exception that when the two grids are unconnected, i.e. the bigger the size of auxiliary grounding grid, the higher the maximum step voltage. The results in this paper could be served as design guideline of grounding system, and perhaps remedy of some troublesome grounding grids in power distribution’s system. Modeling and simulation is carried out on the Current Distribution Electromagnetic interference Grounding and Soil structure (CDEGS) program. The simulation results exhibit the design and analysis of power system grounding and perhaps could be set as a standard in grounding system design and modification in distribution substations.
Abstract: In our modern society electricity is vital to our health,
safety, comfort and well-being. While our daily use of electricity is
often taken for granted, public concern has arisen about potential
adverse health effects from electric and magnetic – electromagnetic –
fields (EMFs) produced by our use of electricity.
This paper aims to compare between the measured magnetic field
values and the simulated models for the indoor medium to low
voltage (MV/LV) distribution substations.
To calculate the magnetic flux density in the substations,
interactive software SUBCALC is used which is based on closed
form solution of the Biot-Savart law with 3D conductor model.
The comparison between the measured values and the simulated
models was acceptable. However there were some discrepancies, as
expected, may be due to the current variation during measurements.
Abstract: Improving the reactive power and voltage profile of a
distribution substation is investigated in this paper. The purpose is to
properly determination of the shunt capacitors on/off status and
suitable tap changer (TC) position of a substation transformer. In
addition, the limitation of secondary bus voltage, the maximum
allowable number of switching operation in a day for on load tap
changer and on/off status of capacitors are taken into account. To
achieve these goals, an artificial neural network (ANN) is designed to
provide preliminary scheduling. Input of ANN is active and reactive
powers of transformer and its primary and secondary bus voltages.
The output of ANN is capacitors on/off status and TC position. The
preliminary schedule is further refined by fuzzy dynamic
programming in order to reach the final schedule. The operation of
proposed method in Q/V improving is compared with the results
obtained by operator operation in a distribution substation.
Abstract: This paper presents the significant factor and give
some suggestion that should know before design. The main objective of this paper is guide the first step for someone who attends to design of grounding system before study in details later. The overview of
grounding system can protect damage from fault such as can save a human life and power system equipment. The unsafe conditions have
three cases. Case 1) maximum touch voltage exceeds the safety
criteria. In this case, the conductor compression ratio of the ground gird should be first adjusted to have optimal spacing of ground grid
conductors. If it still over limit, earth resistivity should be consider afterward. Case 2) maximum step voltage exceeds the safety criteria.
In this case, increasing the number of ground grid conductors around
the boundary can solve this problem. Case 3) both of maximum touch
and step voltage exceed the safety criteria. In this case, follow the solutions explained in case 1 and case 2. Another suggestion, vary depth of ground grid until maximum step and touch voltage do not
exceed the safety criteria.
Abstract: In nature, electromagnetic fields always appear like
atmosphere static electric field, the earth's static magnetic field and
the wide-rang frequency electromagnetic field caused by lightening.
However, besides natural electromagnetic fields (EMF), today human
beings are mostly exposed to artificial electromagnetic fields due to
technology progress and outspread use of electrical devices. To
evaluate nuisance of EMF, it is necessary to know field intensity for
every frequency which appears and compare it with allowed values.
Low frequency EMF-s around transmission and distribution lines are
time-varying quasi-static electromagnetic fields which have
conservative component of low frequency electrical field caused by
charges and eddy component of low frequency magnetic field caused
by currents. Displacement current or field delay are negligible, so
energy flow in quasi-static EMF involves diffusion, analog like heat
transfer. Electrical and magnetic field can be analyzed separately.
This paper analysis the numerical calculations in ELF-400 software
of EMF in distribution substation in shopping center. Analyzing the
results it is possible to specify locations exposed to the fields and
give useful suggestion to eliminate electromagnetic effect or reduce it
on acceptable level within the non-ionizing radiation norms and
norms of protection from EMF.