Effect of Copper Particle on the PD Characteristics in a Coaxial Duct with Mixture of SF6 (10%) and N2 (90%) Gases

Insulation performance of a gas insulated system is severely affected by particle contaminants. These metallic particles adversely affect the characteristics of insulating system. These particles can produce surface charges due to partial discharge activities. These particles which are free to move enhance the local electric fields. This paper deals with the influence of conducting particle placed in a co-axial duct on the discharge characteristics of gas mixtures. Co-axial duct placed in a high pressure chamber is used for the purpose. A gas pressure of 0.1, 0.2 and 0.3 MPa have been considered with a 10:90 SF6 and N2 gas mixtures. The 2D and 3D histograms of clean duct and duct with copper particle are discussed in this paper.

Measurement of Small PD-S in Compressed SF6(10%) - N2(90%) Gas Mixture

Partial Discharge measurement is a very important means of assessing the integrity of insulation systems in a High Voltage apparatus. In compressed gas insulation systems, floating particles can initiate partial discharge activities which adversely affect the working of insulation. Partial Discharges below the inception voltage also plays a crucial in damaging the integrity of insulation over a period of time. This paper discusses the effect of loose and fixed Copper and Nichrome wire particles on the PD characteristics in SF6-N2 (10:90) gas mixtures at a pressure of 0.4MPa. The Partial Discharge statistical parameters and their correlation to the observed results are discussed.